Select Esc 2 times to go back to the main menu > Select Ethernet > Select IP parameters and enter in the IP address, subnet mask and gateway of the parameters you are using in your program on Visilogic.ĩ. Select Version > select software and write down the PLC name to the controller currently stored on the PLC.Ĩ. The default password is 1111 and select the big return arrow button.ħ. Hold your finger anywhere on the screen for 10 seconds until you see an Info Mode screen appear. Power up the PLC if you haven't already done so. Set the client/server to Server(slave).Ħ. Connect a TCP/IP Socket Init FB to the Card Init to setup the socket number you will use, protocol is set to TCP, local port depends on the socket number, # 0 is 20000, # 1 is 20256, # 2 is 502, and # 3 is 20257. Add the function PLC name after TCP/IP card Init and configure your PLC name.ĥ.The PLC Name, TCP/IP Card Init and TCP/IP Socket Init can be found under the Com tab when selecting Main Module under the ladder row in the solution explore field to the left of the software screen.

In the ladder code add the function TCP/IP card Init after a direct contact of SB2 and configure the IP address, Subnet mask and default gateway according to your network settings.The PLC must need to have or comprise an Ethernet card in one of the com ports on the controller.To download to the PLC form your PC using an ethernet connection please follow the steps below: Connection over Ethernet with TCP/IP(call) using Visilogic